Type : 2XSEYFGY / A2XSEYFGY

Special Type

  • 2XSEYFGY- FR
  • 2XSEYFGY- FRLS
  • 2XSEYFGY- LSZH
  • 2XSEYFGY- HRFR-105°C

Specifications / Rating

ASTM: B-3
BDS IEC: 60228 & 60502-2
IEC: 60228 & 60502-2
IS: 7098-2

Applications

  • Indoor
  • Outdoor
  • Underground
  • In water
  • Power plant
  • Switch gear
  • Generator
  • Industrial
  • Substation

Construction : Annealed Copper or Aluminium Conductor / Inner semiconducting layer / XLPE Insulation / Outer semiconducting layer / Metallic screen / Separation sheath / Flat steel wire armour with helical tape / PVC outer sheath.

Voltage : 3.6 / 6 (7.2 KV) (Permissible Service Voltage : 3.8 / 6.6 KV)

tecnical data
Nominal Conductor Area Nominal Thickness of Insulation Nominal dia. of flat steel wire armour Nominal Thickness of Sheath Approx overall dia. of cable Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating in ground at 20°C Current rating in air at 30°C
Cu Al Cu Al Cu Al Cu Al
Core x mm2 mm mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3x25rm 2.5 4×0.8 2.1 43.5 3080 2597 0.7270 1.200 145 113 147 114
3x35rm 2.5 4×0.8 2.2 46.0 3560 2899 0.5240 0.868 182 141 183 112
3x50rm 2.5 4×0.8 2.3 49.0 4160 3116 0.3870 0.641 218 169 218 169
3x70rm 2.5 4×0.8 2.4 53.0 5120 3798 0.2680 0.443 269 209 270 210
3x95rm 2.5 4×0.8 2.5 57.0 6260 4466 0.1930 0.320 324 252 333 259
3x120rm 2.5 4×0.8 2.6 60.0 7130 4870 0.153 0.253 362 282 378 294
3x150rm 2.5 4×0.8 2.7 64.0 8270 5437 0.1240 0.206 411 319 436 338
3x185rm 2.5 4×0.8 2.9 68.0 9780 6286 0.0991 0.164 455 354 503 391
3x240rm 2.6 4×0.8 3.0 74.0 11900 7368 0.0754 0.125 527 409 580 450
3x300rm 2.8 4×0.8 3.2 80.0 14450 8784 0.0601 0.100 567 440 611 474

Voltage : 8.7 / 15 (17.5 KV) (Permissible Service Voltage : 9.7 / 16.25 (KV)

tecnical data
Nominal Conductor Area Nominal Thickness of Insulation Nominal dia. of flat steel wire armour Nominal Thickness of Sheath Approx overall dia. of cable Approx Weight of Cable Max. DC resist. of conductor at 20°C Current rating in ground at 20°C Current rating in air at 30°C
Cu Al Cu Al Cu Al Cu Al
Core x mm2 mm mm mm mm Kg/Km Kg/Km ohm/km ohm/km amps amps amps amps
3x25rm 4.5 4×0.8 2.4 54.0 4100 3617 0.7270 1.200 145 113 147 114
3x35rm 4.5 4×0.8 2.5 56.0 4620 3959 0.5240 0.868 184 143 186 145
3x50rm 4.5 4×0.8 2.6 59.0 5250 4306 0.3870 0.641 220 171 222 172
3x70rm 4.5 4×0.8 2.7 63.0 6280 4958 0.2680 0.443 271 211 275 212
3x95rm 4.5 4×0.8 2.8 67.0 7500 5706 0.1930 0.320 326 253 336 261
3x120rm 4.5 4×0.8 2.9 70.5 8420 6154 0.153 0.253 364 283 380 296
3x150rm 4.5 4×0.8 3.0 73.5 9550 6717 0.1240 0.206 413 320 440 314
3x185rm 4.5 4×0.8 3.2 78.0 11100 7606 0.0991 0.164 457 355 506 393
3x240rm 4.5 4×0.8 3.3 83.5 13400 8868 0.0754 0.125 530 412 585 453
3x300rm 4.5 4×0.8 3.5 89.0 15700 10034 0.0601 0.100 570 442 614 476

Note: For value of Capacitance, Inductance & AC Resistance please refer to page no. 88 in this Catalogue.